EOCRSSD-60S – Electronic Overcurrent Relay (Digital, 10–60A, 220VAC)

The EOCRSSD-60S is a compact and intelligent electronic overcurrent relay designed to protect motors from overloads, phase failures, and locked rotor conditions. With digital precision, easy setup, and built-in diagnostics, this relay is ideal for modern motor protection in industrial automation, HVAC, and pumping systems.

Operating on 220VAC, it supports a wide current range of 10A to 60A, making it suitable for a variety of motor sizes. The EOCRSSD series enhances safety, improves uptime, and supports smarter maintenance through real-time monitoring.

Key Features

  • Digital Display for live current monitoring and fault identification
  • Current Setting Range: 10–60A
  • Operating Voltage: 220VAC (single-phase or three-phase)
  • Protection Functions:
    • Overload
    • Phase failure / phase loss
    • Locked rotor (mechanical jamming)
    • Unbalanced phase
  • Reset Mode: Manual or automatic
  • Mounting Type: DIN rail
  • Control Method: Solid-state relay (SSR)
  • Status LEDs indicate normal operation, trip, and reset
  • Compact Size for space-constrained panels
  • Fast Reaction Time with accurate tripping curves
  • Internal CTs – No external CT required for standard range
  • Test Button for on-site verification of relay operation

Technical Data Sheet

ParameterValue
ModelEOCRSSD-60S
Current Setting Range10 – 60 A
Control Supply Voltage220 V AC ±10%, 50/60 Hz
Trip Time (Overload)Adjustable: 1 – 30 sec
Trip Time (Locked Rotor)Fixed: < 0.5 sec
Reset TypeManual / Auto
Output Contact1 NO (Relay Output)
MountingDIN Rail (35 mm)
Display7-segment LED display
IndicationsLED for Normal, Trip, and Alarm
Operating Temperature–10°C to +60°C
Storage Temperature–20°C to +70°C
Insulation Resistance>100 MΩ at 500 VDC
Dielectric Strength2.5 kV, 1 min
WeightApprox. 200g
Dimensions (W × H × D)Approx. 45 × 90 × 65 mm
CertificationsCE, RoHS

Applications

  • Industrial motors (pumps, conveyors, compressors)
  • HVAC systems
  • Water treatment plants
  • Machine automation panels
  • Building management systems
  • Any motor-based application requiring reliable overload protection

What’s Included

  • EOCRSSD-60S Relay Unit
  • User Manual
  • Mounting Clips